MULTI-PURPOSE IN/OUT BOARD

Description

FUNCTIONING
Eva Power manages lighting, blinds, electric pumps and solenoid valves (heating, irrigation), simple and electronic commands, presence detectors, twilight, wind and rain sensors, customisable timer functions and measures the resulting loads.

CONNECTIONS
Eva Power has 16 digital inputs, 10 relay outputs with independent measurement of absorbed power, a 230 V~ mains supply and a RS485 communications port for communication and programming using Lapis software.

TECHNICAL CHARACTERISTICS
Eva Power is a complete automation board with 16 5V DC digital inputs and 4 terminals for the system, 10 outputs with 230V~ 12A resistive relays and NO-NC double terminals (for total loads of up to 6 kVA), a 230V~ mains power supply and an RS-485 serial communication and programming port. Eva Power measures absorbed power in real time on each output (for loads over 1000 W). The board is set up for fastening with a DIN guide on a 13-module (Master type) control panel and, thanks to the optional side rings, can be screwed onto junction boxes or plasterboard walls. All connections are made using extractable printed terminal blocks to facilitate wiring and replacement.
Eva Power is equipped with an auxiliary power supply device that allows the built-in clock to run and settings to be maintained even in the event of black-out. It is supplied pre-programmed step-step on each output to check functioning. It is fitted with LED indicator lights for easily identifiable relay power supply, functioning and enabling. Eva can be set up as you wish, using the Lapis simplified software programming interface.

CODES
HS02000 230V~ EvaPower (package of 1pc.)
HS02500 127V~ Eva Power (package of 1pc.)